IEC 60227-6:2001 pdf free download Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V – Part 6: Lift cables and cables for flexible connections
1Scope
This part of lEC 60227 details the particular specifications for both circular and flat lift cablesand cables for flexible connections of rated voltages up to and including 450/750 V.
Each cable complies with the appropriate requirements given in lEC 60227-1, and with theparticular requirements of this part of IEC 60227.
2Normative references
The following normative documents contain provisions which,through reference in this text,constitute provisions of this part of lEC 60227.For dated references,subsequent amend-ments to, or revisions of,any of these publications do not apply. However,parties toagreements based on this part of lEC 60227 are encouraged to investigate the possibility ofapplying the most recent editions of the normative documents indicated below. For undatedreferences, the latest edition of the normative document referred to applies.Members of lECand lsO maintain registers of currently valid International Standards.
IEC 60096-0-1:1990,Radio-frequency cables – Part 0-1: Guide to the design of detailedspecifications – Coaxial cables 1
IEC 60227-1:1993,Polyvinyl chloride insulated cables of rated voltages up to and including450/750 v – Part 1: General requirements 2
IEC 60227-2:1997,Polyvinyl chloride insulated cables of rated voltages up to and including450/750 v – Part 2: Test methods
IEC 60228:1978,Conductors of insulated cables
IEC 60332-1:1993,Tests on electric cables under fire conditions – Part 1:Test on a singlevertical insulated wire or cable
IEC 60502-1:1997,Power cables with extruded insulation and their accessories for ratedvoltages from i kv(um = 1,2 kV) up to 30 kV (Um = 36 kV) – Part 1: Cables for rated voltagesof 1 kV (um = 1,2 kv) and 3 kv (Um = 3,6 kv) 3
CEI 60811-1-1:1993,Methodes d’essais communes pour les matériaux d’isolation et degainage des cables électriques – Partie 1: Methodes d’application generale – Section 1:Mesure des épaisseurs et des dimensions extérieures ‘- Determination des proprietésmecaniques
CEI 60811-1-2:1985,Methodes d’essais communes pour les matériaux disolation et degainage des cables electriques – Premiere partie: Methodes d’application genérale – Sectiondeux: Methodes de vieillissement thermique
CEl 60811-1-4:1985,Methodes dessais communes pour les matériaux d’isolation et degainage des cables electriques – Premiere partie: Methodes d’application generale – Sectionquatre: Essais a basse temperature
CEI 60811-3-1:1985: Methodes d’essais communes pour les matériaux disolation et degainage des cables électriques – Troisieme partie: Methodes specifiques pour les melangesPvc- Section une: Essai de pression a temperature élevee ‘- Essais de resistance a lafissuration
CEI 60811-3-2:1985: Methodes d’essais communes pour les matériaux disolation et degainage des cables electriques – Troisieme partie: Methodes specifiques pour les melangesPvc -Section deux: Essai de perte de masse – Essai de stabilite thermique
3Cable meplat sous gaine de polychlorure de vinyle pour ascenseurs et
cables pour connexions souples
3.1 Designation
60227 IEC 71 f
3.2Tension nominale
. 300/500 V pour les cables dont la section nominale des ames conductrices est au plus
egale a 1 mm2;
. 450/750 v pour les ames de section supérieure a 1 mm2.
3.3Constitution
3.3.1 Ame
Nombre d’ames: 3,4,5,6,9,12,16,18,20 ou 24.
Les combinaisons des sections nominales et du nombre des conducteurs ayant ces sectionssont donnees dans le tableau 1 suivant: