IEC 61210:2010 pdf free download Connecting devices – Flat quick-connect terminations for electrical copper conductors – Safety requirements
1 Scope
This International Standard applies to non-insulated flat quick-connect terminations consistingof a male tab of size 2,8 mm, 4,8 mm, 6,3 mm or 9,5 mm with hole or dimple detents and amating female connector for use as either an incorporated or an integrated part of an equipment or of a component, or as a separate entity.This standard establishes uniformrequirements for the dimensions, performance characteristics and test program.
The connected electrical copper conductors shall be flexible or rigid stranded, having a cross-sectional area up to and including 6 mm 2 or rigid solid having a cross-sectional area up to andincluding 2,5 mm 2.This standard shall not be used for connecting aluminum conductors.
The rated voltage shall not exceed 1 000 V a.c. with a frequency up to and including
1 000 Hz, and 1 500 v d.c., and having the temperature limits applicable to materials usedwithin this standard.
NOTE1 This standard, where applicable, may be used for conductors made of material other than copper.NOTE 2 For reasons of safety,it is recommended that flat quick-connect terminations beyond the scope of thisstandard should not be interchangeable with those of this standard.
NOTE 3 This standard does not apply to female connectors with positive locking means.
NOTE4 The flat quick-connect terminations covered by this standard are not intended to be disconnected bypulling on the cabie.
NOTE 5 Annex D provides additional information on non international units.2Normative references
The following referenced documents are indispensable for the application of this document.For dated references, only the edition cited applies.For undated references, the latest editionof the referenced document (including any amendments) applies.
IEC60068-1:1988,Environmental testing Part 1: General and guidance
IEC 60352-2:2006,Solderless connections口 Part 2: Crimped connections- Generalrequirements,test methods and practical guidance
ISO 1456:2009,Metallic and other inorganic coatingsElectrodeposited coatings of nickel,nickel plus chromium, copper plus nickel and of copper plus nickel plus chromium
ISO 2081:2008,Metallic and other inorganic coatings- Electroplated coatings of zinc withsupplementary treatments on iron or steel
ISO 2093:1986, Electroplated coatings of tin Specification and test methods
3Terms and definitions
For the purpose of this document the following terms and definitions apply:
3.1
flat quick-connect termination
electrical connection consisting of a male tab and a female connector which can be insertedand withdrawn with or without the use of a tool
3.2
male tab
that portion of a flat quick-connect termination which receives the female connector
3.3
male test tab
male tab manufactured with tighter tolerances for the specific purpose of conductingmechanical tests with production female connectors
3.4
female connector
that portion of a flat quick-connect termination which is pushed onto the male tab
3.5
detent
dimple (depression) or hole in the male tab which engages a raised portion on the femaleconnector to provide a latch for the mating parts
3.6
maximum permissible temperaturemaximum service temperature
highest temperature which the flat quick-connect termination is allowed to attain in normal use